Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T18CM07526
Parcel: 11942006J

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T18CM07526
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Plan sheet E1. (a) Keyed note #3 makes reference to detail #3. Could not locate detail #3. Please clarify.
(b) Keyed note #8 calls out the circuit breakers to be rated at 22K AIC if the feeder cable is less than 35 feet.. Shouldn't the pedistal also be rated at 22K? See Keyed note #3..
(c) Be advised that because the pedistals are not services per definition, the code requires them to be rated for use as service equipment, but not as SERVICE EQUIPMENT ONLY.. these pedistals
Ref; 2012 IBC sec 107.2.1, 2011 NEC 110.3. 550.32.
09/27/2018 AVAUGHN1 ZONING REVIEW Needs Review