Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T18CM07526
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/21/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref; Plan sheet E1. (a) Keyed note #3 makes reference to detail #3. Could not locate detail #3. Please clarify. (b) Keyed note #8 calls out the circuit breakers to be rated at 22K AIC if the feeder cable is less than 35 feet.. Shouldn't the pedistal also be rated at 22K? See Keyed note #3.. (c) Be advised that because the pedistals are not services per definition, the code requires them to be rated for use as service equipment, but not as SERVICE EQUIPMENT ONLY.. these pedistals Ref; 2012 IBC sec 107.2.1, 2011 NEC 110.3. 550.32. |
| 09/27/2018 | AVAUGHN1 | ZONING | REVIEW | Needs Review |