Permit Number - T18CM07448
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/19/2018 | GPERU1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/19/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 09/19/2018 | MMORENO1 | ENGINEERING | REVIEW | Passed | |
| 09/19/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/19/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/19/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Coordinate the waste & vent diagram for the new work with the plumbing plan. |
| 09/19/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | The existing 2" water meter serves the whole building, not just Suite 131. Revise the water calculations to include the total demand served by the watre meter. |
| 09/19/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Please provide an enlarged restroom floor plan and show maneuvering clearances around ADA fixtures. 2. Provide wall elevations of grab bars, dispensers and show dimensions. 3. Specify the type and number of fasteners-connectors of the new walls to the roof/ceiling. |
| 09/19/2018 | MMORENO1 | ZONING | REVIEW | Approved |