Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM07448
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/19/2018 | MMORENO1 | ZONING | REVIEW | Approved | |
09/19/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
09/19/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/19/2018 | MMORENO1 | ENGINEERING | REVIEW | Passed | |
09/19/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Please provide an enlarged restroom floor plan and show maneuvering clearances around ADA fixtures. 2. Provide wall elevations of grab bars, dispensers and show dimensions. 3. Specify the type and number of fasteners-connectors of the new walls to the roof/ceiling. |
09/19/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | The existing 2" water meter serves the whole building, not just Suite 131. Revise the water calculations to include the total demand served by the watre meter. |
09/19/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Coordinate the waste & vent diagram for the new work with the plumbing plan. |
09/19/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
09/19/2018 | GPERU1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |