Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM07446
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/08/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A-0.08; Toilet Stall Detail 5 (Right View): Please indicate the vertical grab bar. 2. Sheet A-0.08; Accessible Transfer Shower Detail: Per the ICC/ANSI Section 608.3.1.2, a vertical grab bar is required. Please indicate on the control wall. 3. Sheet A-1.22; Eighth Level Plan: An enlarged plan note near both stairs is incomplete. Please revise. 4. Sheet A-1.22; Eighth Level Plan: Please provide a north arrow on the plan. 5. Sheet A-5.01; Sheet Title: Please add a note on the K1C-S plan referencing Sheet A0.02 for the K1RC-S description. 6. Sheet A-5.01; Sheet Title: Please add a note on the K1-S plan referencing Sheet A0.02 for the K1R-S description. 7. Sheet A-5.02; Sheet Title: Please add a note on the K2-S plan referencing Sheet A0.02 for the K2R-S description. 8. Sheet A-5.02; Sheet Title: Please add a note on the K2RC-S plan referencing Sheet A0.02 for the K2CH-S and the K2RCH-S descriptions. 9. Sheet A-5.11; Sheet Title: Please add a note on the QQ1C-S plan referencing Sheet A0.02 for the QQ1RC-S description. 10. Sheet A-5.11; Sheet Title: Please add a note on the QQ1-S plan referencing Sheet A0.02 for the QQ1R-S description. 11. Sheet A-5.11; Sheet Title: Please add a note on the QQ1C-T plan referencing Sheet A0.02 for the QQ1CH-T and the QQ1RCH-T descriptions. 12. Sheet A-5.11; Sheet Title: Please add a note on the QQ1-T plan referencing Sheet A0.02 for the QQ1R-T description. 13. Sheet A-5.21; Sheet Title: Please add a note on the KS1-S plan referencing Sheet A0.02 for the KS1R-S description. 14. Sheet A-5.81; Typical Corridor Plan: The enlarged plan notes near both stairs are incomplete. Please revise. 15. General: Please provide written responses to all review comments. Review by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 10/08/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/08/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 10/08/2018 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | On accessibilty count chart, sheet A-0.02, with tub indicates 7 required, 6 provided. Please clarify. |
| 10/10/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 10/18/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. The Code references in the electrical 'TV RECEPTACLES ROOM NOTE' are incorrect. Should be NEC and IBC. #2. Replacement receptacles should be Tamper Resistant per NEC 406.13. #3. Indicate or show the locations of the panelboards for the units. #4. Designate circuiting for the new smoke detectors. NEC 408.4. Ref; 2012 IBC 107.2.1, 2011 NEC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/18/2018 | AVAUGHN1 | APPROVAL SHELF | Completed |
| 12/18/2018 | AVAUGHN1 | OUT TO CUSTOMER | Completed |
| 12/18/2018 | AVAUGHN1 | REJECT SHELF | Completed |