Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T18CM07446
Parcel: 11504602G

Address:
880 E 2ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM07446
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A-0.08; Toilet Stall Detail 5 (Right View): Please indicate the vertical grab bar.
2. Sheet A-0.08; Accessible Transfer Shower Detail: Per the ICC/ANSI Section 608.3.1.2, a vertical grab bar is required. Please indicate on the control wall.
3. Sheet A-1.22; Eighth Level Plan: An enlarged plan note near both stairs is incomplete. Please revise.
4. Sheet A-1.22; Eighth Level Plan: Please provide a north arrow on the plan.
5. Sheet A-5.01; Sheet Title: Please add a note on the K1C-S plan referencing Sheet A0.02 for the K1RC-S description.
6. Sheet A-5.01; Sheet Title: Please add a note on the
K1-S plan referencing Sheet A0.02 for the K1R-S description.
7. Sheet A-5.02; Sheet Title: Please add a note on the
K2-S plan referencing Sheet A0.02 for the K2R-S description.
8. Sheet A-5.02; Sheet Title: Please add a note on the K2RC-S plan referencing Sheet A0.02 for the K2CH-S and the K2RCH-S descriptions.
9. Sheet A-5.11; Sheet Title: Please add a note on the QQ1C-S plan referencing Sheet A0.02 for the QQ1RC-S description.
10. Sheet A-5.11; Sheet Title: Please add a note on the QQ1-S plan referencing Sheet A0.02 for the QQ1R-S description.
11. Sheet A-5.11; Sheet Title: Please add a note on the QQ1C-T plan referencing Sheet A0.02 for the QQ1CH-T and the QQ1RCH-T descriptions.
12. Sheet A-5.11; Sheet Title: Please add a note on the QQ1-T plan referencing Sheet A0.02 for the QQ1R-T description.
13. Sheet A-5.21; Sheet Title: Please add a note on the KS1-S plan referencing Sheet A0.02 for the KS1R-S description.
14. Sheet A-5.81; Typical Corridor Plan: The enlarged plan notes near both stairs are incomplete. Please revise.
15. General: Please provide written responses to all review comments.

Review by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
10/08/2018 ROBERT SHERRY WATER REVIEW Completed
10/08/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/08/2018 MARTIN BROWN FIRE REVIEW Reqs Change On accessibilty count chart, sheet A-0.02, with tub indicates 7 required, 6 provided. Please clarify.
10/10/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/18/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. The Code references in the electrical 'TV RECEPTACLES ROOM NOTE' are incorrect. Should be NEC and IBC.
#2. Replacement receptacles should be Tamper Resistant per NEC 406.13.
#3. Indicate or show the locations of the panelboards for the units.
#4. Designate circuiting for the new smoke detectors. NEC 408.4.
Ref; 2012 IBC 107.2.1, 2011 NEC.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/18/2018 AVAUGHN1 APPROVAL SHELF Completed
12/18/2018 AVAUGHN1 OUT TO CUSTOMER Completed
12/18/2018 AVAUGHN1 REJECT SHELF Completed