Permit Number: T18CM07437
Parcel: 11504602G

Address:
880 E 2ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM07437
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2018 MARTIN BROWN FIRE REVIEW Reqs Change On accessibilty count chart, sheet A-0.02, with tub indicates 7 required, 6 provided. Please clarify.
10/01/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A-0.08; Toilet Stall Detail 5 (Right View): Please indicate the vertical grab bar.
2. Sheet A-0.08; Accessible Transfer Shower Detail: Per the ICC/ANSI Section 608.3.1.2, a vertical grab bar is required. Please indicate on the control wall.
3. Sheet A-1.21; Second Level Plan: An enlarged plan note near both stairs is incomplete. Please revise.
4. Sheet A-1.21; Second Level Plan: Please provide a north arrow on the plan.
5. Sheet A-5.02; Sheet Title: Please add a note on the
K2-S plan referencing Sheet A-0.02 for the K2R-S description.
6. Sheet A-5.11; Sheet Title: Please add a note on the
QQ1C-T plan referencing Sheet A-0.02 for the QQ1RC-T description.
7. Sheet A-5.11; Sheet Title: Please add a note on the
QQ1-T plan referencing Sheet A-0.02 for the QQ1R-T description.
8. Sheet A-5.11; Sheet Title: Please add a note on the
QQ1C-T plan referencing Sheet A-0.02 for the QQ1CH-T description.
9. Sheet A-5.13; Sheet Title: Please add a note on the
QQ4-T plan referencing Sheet A-0.02 for the QQ4R-T description.
10. Sheet A-5.13; Sheet Title: Please add a note on the
QQ4C-T plan referencing Sheet A-0.02 for the QQ4RC-T description.
11. Sheet A-5.41; Sheet Title: Please add a note on the
KS2-S plan referencing Sheet A-0.02 for the KS2RH-S description.
12. Sheet A-5.82; Second Level Plan: Please add a sheet number to the 2B and 2C wall elevation indicators.
13. General: Please provide written responses to all review comments.

Review by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
10/08/2018 ROBERT SHERRY WATER REVIEW Completed
10/08/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Complete sheet P-5.13
10/08/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/18/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. The Code references in the electrical 'TV RECEPTACLES ROOM NOTE' are incorrect. Should be NEC and IBC.
#2. Replacement receptacles should be Tamper Resistant per NEC 406.13.
#3. Indicate or show the locations of the panelboards for the units.
#4. Designate circuiting for the new smoke detectors. NEC 408.4.
Ref; 2012 IBC 107.2.1, 2011 NEC.