Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Plan Sheet E2. The spreadsheet from APS used for the three phase calculations references the 2008 NEC. The current adopted Code is the 2011.
#2. Verify the inverters have AC disconnects within site of the inverters as required per NEC 690.14D.
#3. Provide an elevation plan showing all the electrical service and PV equipment.
#4. Plan Sheets E1 thru E6 are not sealed and signed by the electrical registrant.
Ref; 2012 IBC sec 107.2.1, 2011 NEC. City of Tucson Commercial Plan Submittal Requirements. www.tucsonaz.gov/pdsd.