Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM07435
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/28/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref; Plan Sheet E2. The spreadsheet from APS used for the three phase calculations references the 2008 NEC. The current adopted Code is the 2011. #2. Verify the inverters have AC disconnects within site of the inverters as required per NEC 690.14D. #3. Provide an elevation plan showing all the electrical service and PV equipment. #4. Plan Sheets E1 thru E6 are not sealed and signed by the electrical registrant. Ref; 2012 IBC sec 107.2.1, 2011 NEC. City of Tucson Commercial Plan Submittal Requirements. www.tucsonaz.gov/pdsd. |