Permit Number: T18CM07435
Parcel: 12217275A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM07435
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Structural Calculations; Loads: A note indicates seismic is exempt for two-story dwellings in Category "C". This is a commercial building and does not meet that criteria. Please provide the structural calculations for seismic.
2. Structural Calculations; Sheets 8 and 9: Sheet 8 indicates the roof joist is a double 8" x 2 1/2" x 16 gage Zee purlin, while the calculation on Sheet 9 uses a C8 x 11.5. A note on Sheet 8 indicates the C8 x 11.5 was selected. The moment of inertia and section modulus for the C8 are 32.5 inches^4 and 8.14 inches^3 from the calculations on Page 10. The moment of inertia and section modulus for the two purlins are 7.936(2) = 15.872 inches^4 and 1.984(2) = 3.968 inches^3. How are these sections comparable? Please verify.
3. General: Please provide written responses to all review comments.
10/17/2018 JOHN VAN WINKLE ENGINEERING REVIEW Approved