Permit Number: T18CM07368
Parcel: 12703544A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM07368
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2018 LOREN MAKUS ENGINEERING REVIEW Passed
10/19/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Designate a branch circuit and panel, also include conduit and or conductor sizes and types for the new washer/dryer outlets.
#2. Show the location of the panels.
#3. Provide complete panel schedules and panel load calcs.
Ref; 2012 IBC sec 107.2.1, 2011 NEC art 408.4.
10/19/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/02/2018 QJONES1 ZONING REVIEW Needs Review
11/02/2018 QJONES1 FIRE REVIEW Needs Review