| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/17/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 10/19/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Designate a branch circuit and panel, also include conduit and or conductor sizes and types for the new washer/dryer outlets. #2. Show the location of the panels. #3. Provide complete panel schedules and panel load calcs. Ref; 2012 IBC sec 107.2.1, 2011 NEC art 408.4. |
| 10/19/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/02/2018 | QJONES1 | ZONING | REVIEW | Needs Review | |
| 11/02/2018 | QJONES1 | FIRE | REVIEW | Needs Review |