Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM07301
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/22/2018 | TOM WEIDEMAN | BUILDING-COMMERCIAL | REVIEW | Completed | |
10/23/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. The PV interconnection on the load side of the Main service disconnect is not allowed unless the exceptions of NEC 705.12D(3) apply. #2. Ref; Plan Sheet E3.3 Detail 4. The equipment ground should be bonded to the conduit, not the Grounded Conductor. NEC art 690.43. #3. Ref; Plan Sheet E1.5, E1.2. (a) Indicate conduit, conductor sizes and types, quantity for the New Service secondary feeders. (b) Provide a Grounding Electrode System detail for the New Service. Include the PV system grounding. Ref; 2011 NEC art 705.12D(3), NEC 250, 2012 IBC sec 107.2.1 |