Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM07301
Parcel: 129101290

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM07301
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2018 TOM WEIDEMAN BUILDING-COMMERCIAL REVIEW Completed
10/23/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. The PV interconnection on the load side of the Main service disconnect is not allowed unless the exceptions of NEC 705.12D(3) apply.
#2. Ref; Plan Sheet E3.3 Detail 4. The equipment ground should be bonded to the conduit, not the Grounded Conductor. NEC art 690.43.
#3. Ref; Plan Sheet E1.5, E1.2.
(a) Indicate conduit, conductor sizes and types, quantity for the New Service secondary feeders.
(b) Provide a Grounding Electrode System detail for the New Service. Include the PV system grounding.
Ref; 2011 NEC art 705.12D(3), NEC 250, 2012 IBC sec 107.2.1

Final Status

Task End Date Reviewer's Name Type of Review Description
10/23/2018 TWEIDEM1 APPROVAL SHELF Completed
10/23/2018 TWEIDEM1 OUT TO CUSTOMER Completed
10/23/2018 TWEIDEM1 REJECT SHELF Completed