Review Details: RESUBMITTAL

Permit Number - T18CM07283
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The 10% referred to in Section 403.2.1 (4), IPC 2012 is the allowable leakage from the exhaust air flow to the supply air flow of an energy recovery unit. Revise the sequence of operation to exhaust all of the air supplied to the restroom during the hours of operation. [Initial comment: Provide information on the sequence of operation for the restroom exhaust fan. Verify that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012.]
11/05/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The manufacturer's data shows the water heater weighs 168 pounds when empty. Revise the structual calculations as needed for a water heater with 30-gallons of water. Indicate how the contractor is to bridge between the trusses to attach the all-thread rods. [Initial comment: Provide structural calculations for the support of the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2012.]
11/16/2018 AVAUGHN1 BUILDING-COMMERCIAL REVIEW Needs Review