Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM07283
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/09/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 1: Provide details for the framing of the walls; show attachment to the roof-ceiling and floor. Specity type and number of fasteners. 2. Previous Comment 2: The architect's seal requires the date of expiration. AZ State Board of Technical Registration requirement. 3. General: Please provide written responses to all review comments. |
| 10/11/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide information on the sequence of operation for the restroom exhaust fan. Verify that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012. |
| 10/11/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide structural calculations for the support of the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2012. 2. Verify that the specified sensor faucet for the public lavatories has an automatic time-out so that it will dispense a maximum of 0.25 gallons per metering cycle. Verify that the cycle time will last for at least 10-seconds for accessibility. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 3. Provide an approved vacuum relief valve for the scheduled bottom-fed water heater that is located above the fixture outlets. Reference: Section 504.2, IPC 2012. 4. Provide a full-open valve for the water supply pipe to the water heater. Reference: Section 606.1(8), IPC 2012. 5. The Watts model 9BD, identified as "RPZ-1" in the plumbing fixture schedule is not a reduced pressure principle backflow prevention assembly (ASSE 1013) as the tag implies. 6. The specified backflow prevention device, Watts model LF7R, is not listed for ASSE 1022 as required for coffee machines or non-carbonated beverage dispensers. Reference: Section 608.16.10, IPC 2012. 7. Provide separate indirect waste pipes for each compartment of the 4-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. 8. Indirect waste piping that has a developed length greater than 30-inches (30") when measured horizontally or greater than 54-inches (54") in total developed length shall be trapped. Exception: indirect waste piping conveying only clear-water waste (e.g. effluent from a sanitizing compartment) does not require a trap. Reference: Section 802.2, IPC 2012. 9. Verify that the developed length of the fixture drain for the floor sink located near the ice bin (equipment #8) complies with the requirements of Table 909.1, IPC 2012. |
| 10/11/2018 | ROBERT SHERRY | WATER | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/30/2018 | QJONES1 | APPROVAL SHELF | Completed |
| 10/30/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
| 10/30/2018 | AVAUGHN1 | REJECT SHELF | Completed |