Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM07223
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/07/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/13/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 11/13/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide an appeal to the building official describing how you plan to relieve the air from the backbar area without allowing the relief air to be recirculated into the building (e.g. duct the relief air away from the AC unit). (https://www.tucsonaz.gov/files/pdsd/forms/Appeal_form4.pdf ) [Initial comment: Provide general room exhaust for any cooking appliance (e.g. two convection ovens) that does not require the installation of a Type II hood. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Sections 501.3 and 507.2.2, IMC 2012.] |
| 11/21/2018 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 11/21/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/27/2018 | AVAUGHN1 | APPROVAL SHELF | Completed |
| 12/27/2018 | AVAUGHN1 | OUT TO CUSTOMER | Completed |
| 12/27/2018 | AVAUGHN1 | REJECT SHELF | Completed |