Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM07223
Parcel: 133165730

Address:
6630 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM07223
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2018 MARTIN BROWN FIRE REVIEW Approved
09/21/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheets G-001 through I-602: The architect of record must indicate on his stamp the date the submitted sheets were signed.
2. Sheet G-005; Plumbing Fixtures: For a restaurant (A-2) occupancy classification, the IBC Table 2902.1 requires water closets at 1 per 75 (male and female), and lavatories at 1 per 200 (male and female). Please revise.
3. Sheet I-504; Details 9, 11, and 13: Note 1 indicates the gypsum board to extend to the floor slab. Please revise this note (no floor slab, and details do not indicate gypsum board continuous to the roof deck above).
4. Sheet I-506; Detail 5 (Hot Water Tank): Please provide the wood blocking connection to the wall studs (blocking size, connection size, and connection quantity), the strapping size, and the connection of the strapping to the wood blocking (or reference this information to specifications, notes, etc.).
5. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911
09/24/2018 ERIC NEWCOMB ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide compliance with the Tucson/Pima County Outdoor Lighting Code. This code can be printed or downloaded from www.tucsonaz.gov/pdsd. See section 104 for Plan submittal requirements. Provide a detailed description for all the exterior luminaires including any site lighting and correlate with the Outdoor Lighting Calcs. If there is exterior site lighting, such as parking, show their location and mark on the site plan.
#2. Ref; Plan Sheet E-1103. There are luminaire identifications or that are not shown in the Luminaire Schedule. Please clarify.
#3. Provide power for the rooftop exhaust fan.
Ref; 2012 IBC sec 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code.
09/28/2018 ROBERT SHERRY WATER REVIEW Completed
10/01/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a direct connection to the building drainage system for all plumbing fixtures except as allowed by Chapter 8, IPC 2012 (i.e. provide a direct waste connection for the bar and hand sinks). Reference: Section 301.3, IPC 2012.
2. Provide a automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucets will operate for at least 10-seconds for accessibility. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. Provide tempered water for the lavatories in the restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
4. The direct-connection of water to an appliance and subject to backpressure (e.g. a misting system) shall be protected against backflow with a reduced pressure principle backflow prevention assembly. Reference: Sections 608.1 and 608.16.6, IPC 2012.
5. The specified backflow prevention device, Wilkins model 700, is not listed for ASSE 1022 as required for coffee machines or non-carbonated beverage dispensers. Reference: Section 608.16.10, IPC 2012.
6. Coordinate the size of the building drain for grease waste. The approved building shell has a 3" grease waste drain entering the grease interceptor. Reference: Section 706.2, IPC 2012.
7. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
8. The hand sink in the workroom is allowed to connect to the sanitary waste system instead of the grease waste system only if the sink has a sign posted above it stating, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.
9. Keynote 14 on sheet P-1102 calls for connecting the grease waste to an existing 1500-gallon gravity grease interceptor. The approved plans (not yet issued) for the building shell called for the installation of a 50-GPM, 100-pound grease interceptor. Verify the required capacity for the planned food service operations. Reference: Section 107.2.1, IBC 2012.
10/01/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show the size, routing, and termination of the condensate drains for the three existing rooftop heat pumps. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.
2. Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.
3. Provide general room exhaust for any cooking appliance (e.g. two convection ovens) that does not require the installation of a Type II hood. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Sections 501.3 and 507.2.2, IMC 2012.
10/03/2018 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM07223 - New Building (Food Service) Related to DP18-0112
Building Plan Review (1st Review) Starbucks Coffee
6630 E Grant Road - C-2 Zoning

TRANSMITTAL DATE: October 3, 2018

DUE DATE: October 10, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. COMMENT: Zoning has reviewed the building plans for compliance with the approved version of the development package. While the building footprint is consistent with the DP as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc) zoning cannot approve the building plans until the building plans have been approved by the PDSD Commercial Plans reviewers.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP.

3. COMMENT: If any changes are necessary, due to the PDSD Commercial Plan Reviewer's comments that affect or change the building footprint, height, or square footage, the DP will need to be updated prior to approval of the building plans by Zoning.

4. COMMENT: Label on the exterior building elevation drawings the heights of the parapet walls.

5. COMMENT: Once the plans have been reviewed and approved by the PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning.


If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans
10/03/2018 LOREN MAKUS ENGINEERING REVIEW Passed