Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T18CM07218
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/17/2018 | GPERU1 | ELECTRICAL-COMMERCIAL | REVIEW | Approved | 1. Specify the size of the panel that will be upgraded to on the plans.. 2. Provide a grounding detail of the new service upgrade. 3. Provide a one-line diagram that the plans are making reference to. 4. Provide panel schedules of existing electrical panels. 5. Submit load calculations for the service upgrade. 6. Show the signature date on the professional sea. 7. Specify the arc-fault calculation for the new service. |