Permit Number: T18CM07218
Parcel: 107060600

Address:
1180 W GLENN ST

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T18CM07218
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2018 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Approved 1. Specify the size of the panel that will be upgraded to on the plans..
2. Provide a grounding detail of the new service upgrade.
3. Provide a one-line diagram that the plans are making reference to.
4. Provide panel schedules of existing electrical panels.
5. Submit load calculations for the service upgrade.
6. Show the signature date on the professional sea.
7. Specify the arc-fault calculation for the new service.