Permit Number: T18CM07216
Parcel: 13819038K

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM07216
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/02/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Section R403.6, IECC 2012 as amended by the City of Tucson.