Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Line Diagram Grounding.
The grounding shown for the new electrical service and transformer calls out for one ground rod. Per NEC art 250.53 , a supplemental grounding electrode is required. Please add this requirement.
Ref; 2012 IBC sec 107.2.1, 2011 NEC.