Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T18CM07056
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/06/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref; Line Diagram Grounding. The grounding shown for the new electrical service and transformer calls out for one ground rod. Per NEC art 250.53 , a supplemental grounding electrode is required. Please add this requirement. Ref; 2012 IBC sec 107.2.1, 2011 NEC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/15/2018 | QJONES1 | APPROVAL SHELF | Completed |
| 11/15/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
| 11/15/2018 | QJONES1 | REJECT SHELF | Completed |