Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T18CM07056
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/14/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 09/20/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/25/2018 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 09/28/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide a grounding detail (Grounding Electrode System)) for the new 200 amp service and 50KVA transformer. Ref; 2012 IBC sec 107.2.1, 2011 NEC art 250, |
| 10/02/2018 | KROBLES1 | COMMUNICATIONS | REVIEW | Approved |