Permit Number: T18CM07056
Parcel: 13101002L

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T18CM07056
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2018 JVINCEN1 FIRE REVIEW Approved
09/20/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/25/2018 DAVID RIVERA ZONING REVIEW Approved
09/28/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide a grounding detail (Grounding Electrode System)) for the new 200 amp service and 50KVA transformer.
Ref; 2012 IBC sec 107.2.1, 2011 NEC art 250,
10/02/2018 KROBLES1 COMMUNICATIONS REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/11/2018 QJONES1 APPROVAL SHELF Completed
10/11/2018 QJONES1 OUT TO CUSTOMER Completed
10/11/2018 QJONES1 REJECT SHELF Completed