Permit Number: T18CM07053
Parcel: 117050020

Address:
400 N 2ND AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM07053
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/27/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. A written response to the previous electrical plan review comments could not be located in this submittal as requested per the previous review.
#2. Comment #1 For outdoor lighting. The floodlight lamp color temperature cannot exceed 3500K. It is shown as 4000K. Tucson/Pima County Outdoor Lighting Code sec 402.1. The detail on plan sheet C4 states, "POWER ROUTED PER ELECTRICAL DESIGN". Please indicate wiring methods of the floodlight and show It on the electrical plan or on the detail on plan sheet C4.. Also assign a branch circuit that is reflected on the panel schedule.
#3. Comment #2, was not addressed. As requested per the previous review (Grounding).
Ref; 2012 IBC sec 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code.