Permit Number: T18CM07053
Parcel: 117050020

Address:
400 N 2ND AV

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T18CM07053
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2018 JVINCEN1 FIRE REVIEW Approved
09/20/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/27/2018 DAVID RIVERA ZONING REVIEW Approved
09/28/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1 Provide compliance with the Tucson/Pima County Outdoor Lighting Code for the exterior pole mounted luminaire. This code can printed or downloaded from www.tucsonaz.gov/pdsd. See section 104 for plan submittal requirements.
#2. Provide a grounding detail for the new 200 amp service.
Ref; 2012 IBC sec 107.2.1, 2011 NEC art 250, Tucson/Pima County Outdoor Lighting Code.
10/02/2018 KROBLES1 COMMUNICATIONS REVIEW Approved
10/02/2018 JOHN VAN WINKLE ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/24/2018 QJONES1 APPROVAL SHELF Completed
12/24/2018 QJONES1 OUT TO CUSTOMER Completed
12/24/2018 QJONES1 REJECT SHELF Completed