Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T18CM07053
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/14/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
09/20/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/27/2018 | DAVID RIVERA | ZONING | REVIEW | Approved | |
09/28/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1 Provide compliance with the Tucson/Pima County Outdoor Lighting Code for the exterior pole mounted luminaire. This code can printed or downloaded from www.tucsonaz.gov/pdsd. See section 104 for plan submittal requirements. #2. Provide a grounding detail for the new 200 amp service. Ref; 2012 IBC sec 107.2.1, 2011 NEC art 250, Tucson/Pima County Outdoor Lighting Code. |
10/02/2018 | KROBLES1 | COMMUNICATIONS | REVIEW | Approved | |
10/02/2018 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/24/2018 | QJONES1 | APPROVAL SHELF | Completed |
12/24/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
12/24/2018 | QJONES1 | REJECT SHELF | Completed |