Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM07052
Parcel: 10609043B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM07052
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/27/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. A written response to the previous electrical plan review comments could not be located in this submittal as requested per the previous review.
#2. Comment #1, was not addressed. Previous review (Grounding).
#3. Comment #2, Part 1, previous review was not addressed for wiring methods of the floodlight.
Part 2, for outdoor lighting. The floodlight lamp color temperature cannot exceed 3500K. It is shown as 4000K. Tucson/Pima County Outdoor Lighting Code sec 402.1.
Ref; 2012 IBC sec 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code.