Review Details: CELL TOWER/ANTENNAS

Permit Number - T18CM07052
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. The NEC requires a supplemental ground rod (2 total) placed no further than 6 feet apart for the grounding electrodes used at the electrical service and the transformer. NEC 250.53(A2),(A3).
#2. There is a 500 watt quartz pole mounted exterior luminaire shown in the details of plan sheet C-4. There is a note that states, "POWER ROUTED PER ELECTRICAL DESIGN". This luminaire is not shown in the electrical drawings or the circuit breaker panel schedule. If it to be utilized, assign a circuit number and show its location on the electrical plans, and show full compliance with the Tucson/Pima County Outdoor Lighting Code for shielding, lumen calcs, and color temperature output requirements. This code can be printed or downloaded from www.tucsonaz.gov/pdsd.
Ref; 2012 IBC sec 107.2.1, 2011 NEC, 2012 Tucson/Pima County Outdoor Lighting Code.