Permit Number: T18CM07052
Parcel: 10609043B

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T18CM07052
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2018 JVINCEN1 FIRE REVIEW Approved
09/20/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/25/2018 DAVID RIVERA ZONING REVIEW Approved
09/27/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide a grounding electrode system detail for the new service equipment and the 50KVA transformer.
#2. The electrical one line diagram shows the 50KVA step down transformer downstream of the 480V service as a new TEP (utility co.) transformer. Please clarify. Normally this would be provided and installed by the contractor not Utility Co.
Ref; 2011 NEC art. 250, 2012 IBC sec 107.2.1.
10/02/2018 KROBLES1 COMMUNICATIONS REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/11/2018 QJONES1 APPROVAL SHELF Completed
10/11/2018 QJONES1 OUT TO CUSTOMER Completed
10/11/2018 QJONES1 REJECT SHELF Completed