Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T18CM07052
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/14/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 09/20/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/25/2018 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 09/27/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide a grounding electrode system detail for the new service equipment and the 50KVA transformer. #2. The electrical one line diagram shows the 50KVA step down transformer downstream of the 480V service as a new TEP (utility co.) transformer. Please clarify. Normally this would be provided and installed by the contractor not Utility Co. Ref; 2011 NEC art. 250, 2012 IBC sec 107.2.1. |
| 10/02/2018 | KROBLES1 | COMMUNICATIONS | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/11/2018 | QJONES1 | APPROVAL SHELF | Completed |
| 10/11/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
| 10/11/2018 | QJONES1 | REJECT SHELF | Completed |