Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM07033
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/17/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 10/09/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheets 4, 5, and 6: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the dimensions. 2. Sheets 4, 5, and 6: Please darken the rack elevations and dimensions so the information is legible. 3. Sheet 8; Common Path of Egress: This note indicates 100 feet per the CBC Table 1017. Please revise this note to the 2012 IBC Table 1014.3, and verify the distance with that table. 4. Sheet 8: Please indicate on this sheet that the requirement of the IBC Table 1016.2 for the exit access travel distance is met. 5. Sheet 8; Width of Egress: Please finish this note. 6. Sheet 18-1799-A; Detail 3: This detail indicates two anchors required per base plate, but Details 2A and 2B indicate four anchors. Are the two anchors indicated in Detail # a minimum required number? Please clarify. 7. General: Please provide a Special Inspection Certificate with Parts A and B completed. You may view this form on www.tucsonaz.gov/PDSD. 8. General: Please provide written responses to all review comments. Review by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |