Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Permit Number - T18CM06952
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/07/2019 | AMARTIN1 | BUILDING-RESIDENTIAL | REVIEW | Needs Review | |
| 09/05/2018 | NROSS1 | NPPO | REVIEW | Passed | |
| 09/05/2018 | NROSS1 | ENGINEERING | REVIEW | Passed | |
| 09/21/2018 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: Nick Ross PROJECT: T18CM06952 8551 E. 23rd St New Carport TRANSMITTAL: 1/28/19 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10. The minimum side setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). The proposed height of the structure is 10ft and requires a 6.67ft setback. Proposed side setback is 3.25ft. The minimum setback to the front street perimeter property line is the greater of twenty (20) feet, or one and one-half (1 ½) the height of the proposed wall ((UDC 6.4.5.C.1.a). The proposed setback is 10'. DDO is required. |