Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM06904
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/28/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet PV1.0 (Array Profile); Sheet PV1.1 (Array Profile): The dimension from grade to the centerline of the column at the beam is listed as 10'-8" on Sheet PV1.0, and 10'-7 1/2" on Sheet PV1.1 (matches Sheet S2.1). Please coordinate. 2. Sheet PV1.1 (Array Plans); Sheet S2.0 (Array Layouts): The P2 and P3 array plans on Sheet PV1.1 are reversed to those shown on Sheet S2.0. Please coordinate. 3. Sheet S2.0 (Array Plans); Structural Calculations (Purlin Design): The calculations indicate a 1000S230-68 on the first sheet, but a 1000S350-68 on the remaining calculations (matches Sheet S2.0). Please coordinate. 4. Sheet S2.0; Plan Keynotes: Note 5 was not located on the plans. Please verify. 5. Sheet S3.0; Detail 201: Notes 1, 2, 5, and 6 were not located on the detail. Please verify. 6. General: Please provide the Special Inspection Certificate with Parts A and B completed. 7. General: Please provide written responses to all review comments. Reviewed by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 10/02/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/02/2018 | AVAUGHN1 | OUT TO CUSTOMER | Completed |