Permit Number: T18CM06875
Parcel: 12410003C

Address:
440 S PARK AV

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T18CM06875
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/05/2018 JOHN VAN WINKLE ENGINEERING REVIEW Passed
09/07/2018 MARTIN BROWN FIRE REVIEW Approved
09/11/2018 DAVID RIVERA ZONING REVIEW Passed
09/18/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/19/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. The feeders for the PV transformer are called out as 250kcmil on the Short Circuit Calcs and at 300kcmil on the Voltage Drop calcs. Please clarify.
#2. The PV load side interconnection must be made at a dedicated circuit breaker or fusible disconnect NEC 705.12D(1).
Ref; 2012 IBC sec 107.2.1, 2011 NEC

Final Status

Task End Date Reviewer's Name Type of Review Description
10/02/2018 TWEIDEM1 APPROVAL SHELF Completed
10/02/2018 TWEIDEM1 OUT TO CUSTOMER Completed
10/02/2018 TWEIDEM1 REJECT SHELF Completed