Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T18CM06875
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/05/2018 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed | |
| 09/07/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/11/2018 | DAVID RIVERA | ZONING | REVIEW | Passed | |
| 09/18/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/19/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. The feeders for the PV transformer are called out as 250kcmil on the Short Circuit Calcs and at 300kcmil on the Voltage Drop calcs. Please clarify. #2. The PV load side interconnection must be made at a dedicated circuit breaker or fusible disconnect NEC 705.12D(1). Ref; 2012 IBC sec 107.2.1, 2011 NEC |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/02/2018 | TWEIDEM1 | APPROVAL SHELF | Completed |
| 10/02/2018 | TWEIDEM1 | OUT TO CUSTOMER | Completed |
| 10/02/2018 | TWEIDEM1 | REJECT SHELF | Completed |