Permit Number: T18CM06874
Parcel: 126191910

Address:
4439 E 22ND ST

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T18CM06874
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Submit a geotechnical soils report as referenced in the structural calculations for the Foundation/Concrete for the monopole on page 3 of 60. 1603.1.6 IBC (This comment was listed on the plan review condructed on 9-14-2018) Second review.
2. The CMU MASONRY WALL DETAIL on sheet S-1 does not match the reinforcement specified on the structural calculation; please clarify. IBC 107.2.1.
3. Please remove reference to CITY OF MARICOPA form sheet S-1. IBC 107.2.1
4. Please provide the names of the individual Special Inspectors for the Special Inspections designated on the SPECIAL INSPECTOR CERTIFICATE. IBC 1704.2
10/09/2018 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Sheet E-4; Cite the proper electric utility provider and AIC rating shown on the ONE-LINE DIAGRAM which is TEP, not SRP, as shown on the service reference. (This comment is carryied over from the plan review conducted on 9-14-18 which was not corrected.) Second review.
10/17/2018 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Approved
10/18/2018 DAVID RIVERA ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/13/2018 QJONES1 APPROVAL SHELF Completed
11/13/2018 QJONES1 OUT TO CUSTOMER Completed
11/13/2018 QJONES1 REJECT SHELF Completed