Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T18CM06874
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/11/2018 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T18CM06874 New Cell Tower Location (1st Review) Broadleaf Tree Design 4439 E 22nd Street - C-2 Zoning TRANSMITTAL DATE: September 11, 2018 DUE DATE: September 24, 2018 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 01. COMMENT: Zoning has done a cursory review of the plans but cannot approve them at this time. This is a proposal for a new cell tower using a Broadleaf tree design and must be approved through a Special Exception review and approval process first. 02. COMMENT: Once the SE process has been completed, the planning review section will have to review these plans for compliance with the special exception PDP and stamp and sign before Zoning can approve and signoff on the plans. 03. COMMENT: Zoning will do a review on the next submittal and do a compliance review of the plans with the Special Exception approval and conditions if any and verify that the Peter Mclaughlin has approved and signed the plans. 04. COMMENT: Add as reference the Special Exception case number next to the title block of all plan sheets. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Cell Tower Plans |
09/12/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide structural calculations for the 9 ft. CMU wall. IBC 107.2.1 2. Submit a geotechnical soils report as referenced in the structural calculations. 1603.1.6 IBC 3. Specify the location of the back-up generator on the site plan; indicate fuel type. IBC 107.2.1 |
09/14/2018 | GPERU1 | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet E-4; Cite the proper electric utility provider and AIC rating shown on the ONE-LINE DIAGRAM which is TEP, not SRP, as shown on the service reference. 2. Provide an automatic transfer switch for transferring power to the generator; show on one-line diagram. Provide verification of compliance with NEC 702. |
09/18/2018 | KROBLES1 | COMMUNICATIONS | REVIEW | Approved | |
09/18/2018 | PETER MCLAUGHLIN | PLANNING-CITY HALL | REVIEW | Reqs Change | WILL APPROVE AFTER APPEAL PERIOD 9/21/18 PM |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/20/2018 | AVAUGHN1 | APPROVAL SHELF | Completed |
09/20/2018 | AVAUGHN1 | OUT TO CUSTOMER | Completed |
09/20/2018 | AVAUGHN1 | REJECT SHELF | Completed |