Permit Number: T18CM06867
Parcel: 140291990

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM06867
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/05/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Evaluation of the control system is not the responsibility of the contractor. [Initial comment: Variable air volume systems vary the amount of air recirculated to spaces base on the heating and cooling requirements of the spaces. The minimum ventilation air required for each space, based on the requirements of Table 403.3, IMC 2012, is constant during occupied hours and independent of the heating and cooling requirements. Verify that the existing air handlers have controls to provide the required ventilation flow rates during occupied hours. Reference: Section 403.6, IMC 2012.]