Permit Number: T18CM06821
Parcel: 113112140

Address:
1806 N CHERRY AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM06821
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2018 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T18CM06821
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. Provide a signed Confirmation of Notice of Demolition form before obtaining the building permit that includes an exterior wall removal, R104.7.

SECTIONS - DETAILS:

1. Show exterior wood siding, sheathing and wall framing with a 6" clearance above the ground (R317.1 item 5). Update detail #5 on sheet P6, also clarify keynote #5.
2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

PLUMBING PLANS:

1. Show hot water pipe with minimum R-3 insulation, N1103.4.2. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Provide a gas line isometric or table for showing the BTU demand and length of line to each gas appliance.
2. Provide the BTU demand of each appliance, total demand, and total developed length from meter to the most remote appliance on the system, and verify the size of the supply pipe for the connected demand (may require upgrading), G2413.3 & Table G2413.4(1). The BTU demands shown on sheet P8 are undersized.

MECHANICAL PLANS:

1. Provide (an HVAC system with) whole-house mechanical ventilation with continuous or a minimum controlled intermittent airflow rate, R303.4 & M1507.3. Show a source of outside supply air or continuous exhaust fan function.

ELECTRICAL PLANS:

1. Show or notate the requirement for a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style, or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. Adjustable security light fixtures are unshielded, not FCO.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review