Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM06761
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/28/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/28/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/28/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/28/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 08/28/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/30/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 08/30/2018 | QJONES1 | ZONING | REVIEW | Approved | APPROVED PER LAUREN MAKUS |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/30/2018 | QJONES1 | APPROVAL SHELF | Completed |
| 08/30/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
| 08/30/2018 | QJONES1 | REJECT SHELF | Completed |