Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T18CM06730
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet Cover: Please indicate the Tango (T) shelves on the plan. 2. Sheet SED 1 of 2; General Project Notes: Note 4 indicates (1) anchor per base plate, while the base plate detail 1 indicates 4 anchor holes in the base plate. Please clarify on the drawing. 3. Sheet SED 1 of 2; General Project Notes: Note 5 indicates periodic special inspections for the anchor installations. Please provide a Special Inspection Certificate with Parts A and B completed. 4. Sheet SED 1 of 2; General Project Notes: Note 10 indicates field welds, if any, require special inspections. It would appear from these drawings there will be field welds. Please verify and include on the Special Inspection Certificate as required. 5. General: Please provide the Special Inspection Certificate with Parts A and B completed. 6. General: Please provide written responses to all review comments. Review by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/18/2019 | AVAUGHN1 | OUT TO CUSTOMER | Completed |