Permit Number: T18CM06730
Parcel: 136027120

Address:
8190 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM06730
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/15/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Previous two comments not addressed: If mechanical system is being altered or replaced, a mechanical plan will be required. Please verify. (exhaust fan for new restroom?)
10/15/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change The restrooms will require exhaust fans per the Mechanical review. Please show the exhaust fan locations and power supply,controls. NEC 408.4
10/15/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The ASSE 1070-listed mixing valve is required to be installed with the new lavatory. Watts does not endorse the use of the LFMMV mixing valve at the hot water source. [Initial comment: The ASSE 1070 thermostatic mixing valve is for point-of-use applications. It is required at the lavatory.]
2. A Watts model LF7R dual check valve is not listed to ASSE 1022 (see the note for the ice maker). [Initial comment: Specify the backflow prevention devices required for the coffee maker and the ice machine (e.g. an ASSE 1022 dual check valve is required for the coffee maker)].
3. The fixture unit schedule, when used to determine the water demand seen by a water meter, needs to include all of the plumbing fixtures served by the water meter.
4. The registrant's seal must be signed and dated.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/19/2018 QJONES1 APPROVAL SHELF Completed
10/19/2018 QJONES1 OUT TO CUSTOMER Completed
10/19/2018 QJONES1 REJECT SHELF Completed