Permit Number: T18CM06730
Parcel: 136027120

Address:
8190 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM06730
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change The comments from the structural/architect plan review have not been corrected on the plans. All corrections need to be placed on the architecutal plans and clouded for identification.
09/14/2018 ROBERT SHERRY WATER REVIEW Completed
09/14/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Coordinate the water heater detail with the water riser diagram (e.g. water heater detail does not show recirculation piping.
2. The ASSE 1070 thermostatic mixing valve is for point-of-use applications. It is required at the lavatory.
3. Specify the backflow prevention devices required for the coffee maker and the ice machine (e.g. an ASSE 1022 dual check valve is required for the coffee maker).
09/14/2018 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change The electrical plan review comments have not been addressed. Please provide lighting calculations or Com Check compliance for interior lighing per the previous electrical comment.
09/14/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Previous comment not addressed: If mechanical system is being altered or replaced, a mechanical plan will be required. Please verify.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/27/2018 QJONES1 APPROVAL SHELF Completed
09/27/2018 QJONES1 OUT TO CUSTOMER Completed
09/27/2018 QJONES1 REJECT SHELF Completed