Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T18CM06730
Parcel: 136027120

Address:
8190 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM06730
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2018 NROSS1 ZONING REVIEW Approved
08/27/2018 GPERU1 MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. If mechanical system is being altered or replaced, a mechanical plan will be required. Please verify.
08/27/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide complete compliance for the 2012 IECC for the lighting. Also the seal is expired.
08/27/2018 NROSS1 ENGINEERING REVIEW Passed
08/27/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet D1.0; Demolition Floor Plan: A key at the southwest corner of the building has no photo number. Please provide.
2. Sheet D1.2; New Lintel: The calculation on this sheet indicates to extend the new channels 2' past the opening. Section 1 on this sheet indicates the channels to extend 16" past the opening (2" + 4" + 4" + 4" + 2"). Please coordinate.
3. Sheet A1.1; Code Information: The minimum number of exits is determined by the IBC Section 1015.1. For occupant loads greater than 49 and less than 500, two exits are required. Please revise the notes on A1.1 (2 exits required, 4 exits provided).
4. Sheet A1.1; Code Information: The maximum exit travel distance reference should be Table 1016.2. Please revise the note.
5. Sheet A1.1; Code Information: Since this is a mixed occupancy (M/S-1), provide restroom calculations per the IBC Section 2902.1.1.
6. Sheet A1.2; Details 3 through 9: Please indicate the size of the metal stud kickers, and indicate the size and quantity of connectors to the top of the partition. Extend the detail to show how the kickers connect at the structure above.
7. General: Please provide written responses to all review comments.
08/27/2018 GPERU1 WATER REVIEW Reqs Change 1. Provide a plumbing site plan. Indicate the location, type and size of the water meter and backflow prevention valve.
08/27/2018 GPERU1 PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a DWV plumbing isometric plan; show sizes of drain and vent piping. P1.0
2. Provide a plumbing fixture schedule for verification of water pipe sizing and water service. P1.1
3. Indicate the sizes of all existing drain pipe that recieves discharge of new plumbing fixtures. P1.0
4. The ice machine will require a backflow prevention valve; specify type and model of BF prevention valve. P1.0
5. Indicate the sizes of all watermains for connection to new plumbing fixtures. P1.1
6. Provide a site plan that shows the location of the water service pipe, backflow prevention valve and size/type and model of the water meter. P1.1
7. Identify all valves on the water distribution piping. P1.1
8. Indicate the location and sizes of new cleanouts. P1.0
9. Specify the sizes of all new drain piping; indicate vent pipe sizes. P1.0
08/27/2018 MARTIN BROWN FIRE REVIEW Approved
08/27/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed