Permit Number: T18CM06688
Parcel: 13505149G

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T18CM06688
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/04/2018 JVINCEN1 FIRE REVIEW Approved
09/07/2018 ROBERT SHERRY BUILDING-COMMERCIAL REVIEW Completed
09/13/2018 KROBLES1 COMMUNICATIONS REVIEW Approved
09/19/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide a grounding detail for grounding the new 200 amp service. Ground per NEC 250.24.
#2. Indicate conduit, conductor sizes and types for the connection between the main service disconnect and the meter base.
Ref; 2012 IBC sec 107.2.1, 2011 NEC

Final Status

Task End Date Reviewer's Name Type of Review Description
11/15/2018 QJONES1 APPROVAL SHELF Completed
11/15/2018 QJONES1 OUT TO CUSTOMER Completed
11/15/2018 QJONES1 REJECT SHELF Completed