Review Details: CELL TOWER/ANTENNAS
Permit Number - T18CM06688
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/04/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 09/07/2018 | ROBERT SHERRY | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 09/13/2018 | KROBLES1 | COMMUNICATIONS | REVIEW | Approved | |
| 09/19/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide a grounding detail for grounding the new 200 amp service. Ground per NEC 250.24. #2. Indicate conduit, conductor sizes and types for the connection between the main service disconnect and the meter base. Ref; 2012 IBC sec 107.2.1, 2011 NEC |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/15/2018 | QJONES1 | APPROVAL SHELF | Completed |
| 11/15/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
| 11/15/2018 | QJONES1 | REJECT SHELF | Completed |