Permit Number: T18CM06667
Parcel: 133152920

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T18CM06667
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2018 JVINCEN1 FIRE REVIEW Approved
08/31/2018 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change Provide grounding details for all new electrical equipment; specify size of ground and connection details.
08/31/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change A structural analysis is required on the existing monopole tower based on a rigorus structural analysis to determine the overall stability and adequacy of the structural members, foundation and connection details. IBC 1603.1
09/10/2018 KROBLES1 COMMUNICATIONS REVIEW Approved
09/11/2018 SMONTES1 PLANNING-CITY HALL REVIEW Reqs Change

Final Status

Task End Date Reviewer's Name Type of Review Description
10/12/2018 QJONES1 APPROVAL SHELF Completed
10/12/2018 QJONES1 OUT TO CUSTOMER Completed
10/12/2018 QJONES1 REJECT SHELF Completed