Permit Number: T18CM06664
Parcel: 13322471B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM06664
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/05/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Approved
09/05/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The architectural and plumbing notes call for the installation of two "filtered drinking water dispensers" but the revised plumbing fixture schedule calls out a sink with a bubbler. The bubbler is not a "filtered drinking water dispenser" and it does not apear to be accessible; show how it is accessible.
09/05/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/05/2018 MARTIN BROWN FIRE REVIEW Reqs Change Per section 907.2.6 of the 2018 International Fire Code, a fire alarm system is required. Please add note to plans regarding a deferred submittal for fire alarms.