Permit Number: T18CM06664
Parcel: 13322471B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM06664
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2018 NROSS1 ZONING REVIEW Approved
08/23/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/23/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/23/2018 NROSS1 ENGINEERING REVIEW Passed
08/23/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0; General Building Summary: Since this TI increases the area and the occupant load, a new plumbing fixture analysis must be provided. Please include calculations for required water closets, lavatories, and drinking fountains (drinking fountain was not located on the plans).
2. Sheet A2.0; Floor Plan: The new restrooms are required to be accessible. Restroom #117 meets the criteria of the ICC/ANSI Figure 604.3, but restroom #120 does not. Please revise as required.
3. Sheet A4.0; Restroom Elevations 3 (C and D): Please provide the locations of all grab bars per the ICC/ANSI Figures 604.5.1 and 604.5.2.
4. Sheet A5.0; Detail 5: Indicate the bracing size and connections to the top of the partition wall. In addition, extend the detail to indicate how the braces are attached at the structure above.
5. General: Please provide written responses to all review comments.
08/23/2018 ROBERT SHERRY WATER REVIEW Completed
08/23/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide drinking fountains for the occupants.
08/23/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/05/2018 SVALENZ1 FIRE REVIEW Needs Review