Permit Number: T18CM06662
Parcel: 120077020

Address:
4009 S 12TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM06662
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2018 MARTIN BROWN FIRE REVIEW Approved
08/31/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide a building code evaluation of the project which includes:
a. Indicate the occupancy classification of the building in accordance with Chapter 3 of the IBC.
2. Specify the occupant load of the building in accordance with Table 1004.1.2 of the IBC
3. Label all exit doors.
4. The new restroom is required to be accessible; provide an enlarged floor plan of the restroom and show maneuvering clearances and wall elevations of grab bars and dispensers. Show the elevations of plumbing fixtures.
6. Indicate deferred submittals of construction materials and systems not contained in the construction drawings.
7. The main exit from the re-built section of the building cannot exit through the garage.
8. Provide attic ventilation calculations for sizing of attic vents.
9. Detail E on sheet D-1 cannot contain the notation "ANCHOR BOLTS AS NECESSARY"; specify the size and spacing of all anchor bolts.
10. Provide minimum plumbing fixture calculations for required number of restroom facilities based on the occupant load of the building.
11. Specify the occupant loads of adjacent areas of the building.
12. Provide the areas of the new construction and existing building.
08/31/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show that the new fenestration is NFRC-certified and complies with the requirements of Table C402.3, IECC 2012 for U-factor and solar heat gain coefficient (SFGC).
2. Show that the rooms have adequate ventilation per Section 402 (natural ventilation) or Section 403 (mechanical ventilation). Reference: Section 401, IMC 2012.
08/31/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/31/2018 ROBERT SHERRY WATER REVIEW Completed
09/21/2018 MMORENO1 ZONING REVIEW Approved
09/21/2018 MMORENO1 ENGINEERING REVIEW Passed
09/21/2018 SVALENZ1 PLUMBING-COMMERCIAL REVIEW Needs Review
09/21/2018 SVALENZ1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review