Permit Number: T18CM06414
Parcel: 14118618A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM06414
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/20/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the sediment trap shown on the gas isometric to show that the gas flow changes direction at the sediment collection point (see Section 408.4, IECC 2012). [Initial comment: Provide riser diagram for the gas piping system.]
2. The submitted site plan does not show the location of the water service piping and the water meter. [Initial comment: Provide a plumbing site plan which shows location of water service piping and water meter.]
08/20/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed