Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T18CM06226
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/14/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Plan review by: Gilbert Peru p: 520-837-6962 Gilbert.Peru@tucsonaz.gov 1. Sheet GN-1 (Concrete Notes); Sheet SE-1 (Notes): Note 2 on Sheet GN-1 indicates an assumed allowable soil bearing value of 2000 psf. Sheet SE-1 (Note 2) references a geotechnical report that indicates an allowable soil bearing capacity of 1500 psf. Please coordinate. Note: This plan review comment was not corrected on the second submittal. 2. Sheet SE-7; Special Inspections: Please provide a Special Inspection Certificate indicating all special inspections required and the ICC certified individual who will be performing each inspection. This certificate may be located on the City of Tucson website www.tucsonaz.gov/pdsd. Note: This plan review comment was not corrected on the second submittal. 3. . General: One set of the 11" x 17" sheets includes Drawing #EEI-NOTES, Drawing 101400SI, MONOPOLE DRAWINGS cover sheet, and Drawings E01 through E08. The E01 sheet, the E02 sheet, the EII-NOTES drawing, and the 101400SI drawing have all been sealed by the licensed engineer of record in another set of drawings, but Sheets E03 through E08 have no seal or signature. Please provide seals, signatures, and dates on those sheets. Note: This plan review comment was not corrected on the second plan submittal. Please provide written responses to these comments. |
| 11/14/2018 | GPERU1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | Plan review by: Gilbert Peru p: 520-837-6962 Gilbert.Peru@tucsonaz.gov Please address the following electrical plan review comments. Also provide a written response. #1. Ref; Electrical plan line diagram and details. (a) Provide a complete one- line diagram for the electrical service and downstream equipment as required per the City of Tucson Commercial Plan Submittal Requirements (electrical). This document can be printed or downloaded from www.tucson az.gov/pdsd. Include conduit, conductor sizes and types, OCPD's for all the equipment feeders and disconnects. Note: this comment was not corrected on the second plan submittal. (b) The GEC for the electrical service should be terminated in the Main service disconnecting means and bonded to the neutral conductor. NEC 250.24c. Not in meter base. Note: this comment was not corrected on the second plan submittal. (c) The wall mount detail on plan sheet E4 shows only one ground rod used for the service grounding, provide for 2 ground rods spaced at 6' or more apart as required per NEC 250.53. If the GEC is integral with the round ring, please show this on the plan. Note: this plan review comment was not corrected on the second submittal. #2. Please be more specific as to how the relocated lighting conductors are to be extended to the new light pole location. Ref; 2012 IBC sec 107.2.1, 2011 NEC. Note: this plan revoew comment was not corrected on the second submittal. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/05/2019 | AMARTIN1 | OUT TO CUSTOMER | Completed |