Permit Number: T18CM06226
Parcel: 10819004A

Address:
4502 N 1ST AV

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T18CM06226
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2018 MARTIN BROWN FIRE REVIEW Approved
08/17/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet GN-1 (Concrete Notes); Sheet SE-1 (Notes): Note 2 on Sheet GN-1 indicates an assumed allowable soil bearing value of 2000 psf. Sheet SE-1 (Note 2) references a geotechnical report that indicates an allowable soil bearing capacity of 1500 psf. Please coordinate.
2. Sheet SE-1; Note 2: This note indicates a geotechnical report was provided for this project. Please provide one copy of this report for review.
3. Sheet SE-2; Roof Framing Plan: The section cut 3/SE4 at the center post is not correct. Please revise.
4. Sheet SE-2; Roof Framing Plan: A note at the south corner of the building references 2/SE-2 for a post. Please revise that reference.
5. Sheet SE-2; Roof Framing Plan: A note at the southwest wall references 2/SE-2 for a W8. Please revise that reference.
6. Sheet SE-2; Reflected Ceiling Plan: A note at the west corner of the building references 2/SE-2 for a W8. Please revise that reference.
7. Sheet SE-2; Reflected Ceiling Plan: A note at the east corner of the building references 1/SE-6 for plywood sheathing. Please revise that reference.
8. Sheet SE-2; Reflected Ceiling Plan: A note at the southeast wall references 2/SE-2 for a 4x4 angle. Please revise that reference.
9. Sheet SE-2; Roof Sub-Framing Plan: Please revise all sections and detail notes as required.
10. Sheet SE-4; Section 1: A boxed note below the section references Note 6.3 on Sheet SE-3 for engineered fill. Please revise that reference.
11. Sheet SE-4; Section 1: A note references 3/SE-3 for the slab reinforcing. Please revise that reference.
12. Sheet SE-4; Section 2: A note references 13/SE-6 at the cold formed channel notes. Please revise that reference.
13. Sheet SE-5; Detail 3: A note references 4/SE-2 for wall verticals. Please revise that reference.
14. Sheet SE-6; Foundation Notes: Note 2 on Sheet SE-1 indicates a geotechnical report was provided for this project. Please provide one copy of that report for review, and revise Foundation Note 6.1 on this sheet as required.
15. Sheet SE-7; Special Inspections: Please provide a Special Inspection Certificate indicating all special inspections required and the ICC certified individual who will be performing each inspection. This certificate may be located on the City of Tucson website www.tucsonaz.gov/pdsd.
16. General: Please provide structural calculations for the equipment shelter roof, walls, and foundation designs.
17. General: One set of the 11" x 17" sheets includes Drawing #EEI-NOTES, Drawing 101400SI, MONOPOLE DRAWINGS cover sheet, and Drawings E01 through E08. The E01 sheet, the E02 sheet, the EII-NOTES drawing, and the 101400SI drawing have all been sealed by the licensed engineer of record in another set of drawings, but Sheets E03 through E08 have no seal or signature. Please provide seals, signatures, and dates on those sheets.
18. General: Please provide written responses to all review comments.
08/30/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Electrical plan line diagram and details.
(a) Provide a complete one- line diagram for the electrical service and downstream equipment as required per the City of Tucson Commercial Plan Submittal Requirements (electrical). This document can be printed or downloaded from www.tucson az.gov/pdsd. Include conduit, conductor sizes and types, OCPD's for all the equipment feeders and disconnects.
(b) The GEC for the electrical service should be terminated in the Main service disconnecting means and bonded to the neutral conductor. NEC 250.24c. Not in meter base.
(c) The wall mount detail on plan sheet E4 shows only one ground rod used for the service grounding, provide for 2 ground rods spaced at 6' or more apart as required per NEC 250.53. If the GEC is integral with the round ring, please show this on the plan.
#2. Please be more specific as to how the relocated lighting conductors are to be extended to the new light pole location.
Ref; 2012 IBC sec 107.2.1, 2011 NEC.
10/17/2018 KROBLES1 COMMUNICATIONS REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/21/2018 QJONES1 APPROVAL SHELF Completed
09/21/2018 QJONES1 OUT TO CUSTOMER Completed
09/21/2018 QJONES1 REJECT SHELF Completed