Permit Number: T18CM06133
Parcel: 110052730

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T18CM06133
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2019 ARUIZ1 NPPO REVIEW Needs Review
06/20/2019 ARUIZ1 ENGINEERING REVIEW Needs Review
06/20/2019 ARUIZ1 BUILDING-RESIDENTIAL REVIEW Needs Review
08/07/2018 NROSS1 ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Mark Castro
Lead Planner

PROJECT:
T18CM06133
4426 E. Blacklidge Dr
New Carport

TRANSMITTAL: 3/22/19 **Revised**
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

The minimum setback to the front street perimeter property line is the greater of twenty (20) feet, or one and one-half (1 ½) the height of the proposed wall ((UDC 6.4.5.C.1.a).

Based on a carport wall height of 7'-8", the required setback from the carport to the north lot line is 20', proposed is 4'.

DDO approval is required prior to zoning approval.