Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM06109
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/07/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/07/2018 | EHAMBLI1 | ENGINEERING | REVIEW | Passed | |
| 08/07/2018 | GPERU1 | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Verify compliance with Tucson-Pima County Outdoor Lighting Code. 2. E12.1 Show the location of the fault-current node on the one-lind diagram. 3. Panel type refers to C.B. NOTE; which cannot be located on the plans. 4. E5.1 Circuit designation LA-18 is mislabeled on the subpanel schedule; please correct. |
| 08/07/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/07/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/07/2018 | EHAMBLI1 | ZONING | REVIEW | Approved | |
| 08/10/2018 | SVALENZ1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 08/10/2018 | SVALENZ1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 08/10/2018 | SVALENZ1 | WATER | REVIEW | Needs Review |